  4. Utilizing waste heat from data centers with adsorptive heat transformation - Heat exchanger design and choice of adsorbent
 
  • Details
  • Full
Options
June 2024
Journal Article
Title

Utilizing waste heat from data centers with adsorptive heat transformation - Heat exchanger design and choice of adsorbent

Abstract
The electricity and water consumption of data centers is growing on a global scale. A shift towards liquid cooled racks in combination with thermally driven cooling can help to reduce the electricity and water demand associated with the necessary heat rejection. To quantify the potential of adsorptive heat transformation devices in reducing the electricity and water demand, the prediction of thermal efficiency, heat flow rates and energy efficiency ratio is required. To this end, a numerical model is newly developed using basic adsorption heat exchanger theory. This model can predict the necessary performance indicators with respect to temperatures and volume flow rates, heat exchanger design and adsorbent. The full performance map of a market-available adsorption chiller (71 points) and own measurements are used for calibration and rigorous validation of the model. An average deviation (experiment vs. calculation) of 8.3 % in terms of thermal efficiency and 7.2 % in terms of heat flow rates is achieved, indicating a very good agreement for a wide range of temperatures. At a moderate liquid cooled rack outlet temperature of 50 °C, a heat rejection temperature of 26 °C and a cold aisle inlet temperature of 18 °C the cooling power of the silica gel reference chiller of 5.3 kW can be increased by 59 % to 8.5 kW at a partial energy efficiency ratio (pumps and control, no fans) of > 20 by assuming MIL-100(Fe) as adsorbent on a flat-tube lamella heat exchanger. The model can be used in subsequent annual system simulations to quantify the savings in electrical power and water consumption, which strongly depend on the ambient conditions.
Author(s)
Velte-Schäfer, Andreas  
Fraunhofer-Institut für Solare Energiesysteme ISE  
Teicht, Christian  orcid-logo
Fraunhofer-Institut für Chemische Technologie ICT  
Stahlhut, Maximilian
University of Technology Chemnitz
Mayer, Thomas
Fahrenheit GmbH, Halle
Herrmann, Ralph
Fahrenheit GmbH, Halle
Urbaneck, Thorsten
Füldner, Gerrit  
Fraunhofer-Institut für Solare Energiesysteme ISE  
Journal
Energy conversion and management  
Open Access
File(s)
Download (2.54 MB)
Rights
CC BY 4.0: Creative Commons Attribution
DOI
10.1016/j.enconman.2024.118500
10.24406/publica-3048
Additional link
Landing Page
Language
English
Fraunhofer-Institut für Chemische Technologie ICT  
Fraunhofer-Institut für Solare Energiesysteme ISE  
Keyword(s)
  • Adsorption chiller

  • Data center

  • Effective heat and mass transfer resistances

  • Metal organic framework