  4. Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part A: Testing campaign and experimental results
 
  • Details
  • Full
Options
2021
Journal Article
Title

Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part A: Testing campaign and experimental results

Other Title
Mauvaise distribution du frigorigène dans les évaporateurs d'échangeurs de chaleur à plaques
Abstract
The refrigerant distribution in a brazed plate heat exchanger evaporator with distributor has been studied with a thermographic camera working under different conditions of inlet vapor quality, superheat, and water temperature drop. The thermographies have shown a clear uneven thermal distribution except when superheat is null. In most of the cases, they show that a great part of the liquid accumulates at the end channels of the evaporator. The degradation of the evaporator performance is higher when the water temperature drop has a similar or higher value than the superheat. On the other hand, when the superheat is significantly higher than the water temperature drop, the evaporator performance is very similar to situations in which there is an even distribution of the refrigerant. The registered evaporation temperatures are much lower for the case of 13 K of water temperature drop, highlighting the importance of the influence of this parameter on the evaporator performance. This research is described in two parts, Part A (present paper) including the description of the experimental campaign, the obtained experimental results and the results discussion and Part B including an analysis of the degradation of the evaporation temperature due to the refrigerant maldistribution as well as a deeper analysis of the registered temperatures and of the causes for the great degradation observed when the water temperature drop is increased.
Author(s)
Navarro-Peris, E.
Polytechnic University of Valencia (UPV)
Alvarez-Piñeiro, L.
Polytechnic University of Valencia (UPV)
Albaladejo, P.
Polytechnic University of Valencia (UPV)
Schnabel, Lena  
Fraunhofer-Institut für Solare Energiesysteme ISE  
Corberan, Jose M.
Polytechnic University of Valencia (UPV)
Journal
International journal of refrigeration  
Open Access
File(s)
Download (3 MB)
Rights
CC BY 4.0: Creative Commons Attribution
DOI
10.24406/publica-r-415739
10.1016/j.ijrefrig.2021.04.002
Language
English
Fraunhofer-Institut für Solare Energiesysteme ISE  
Keyword(s)
  • Wasserstofftechnologie

  • Energieeffiziente Gebäude

  • Lüftungs- und Klimatechnik

  • Brazed Plate Heat Exchanger

  • energy performance

  • Evaporator

  • Maldistribution

  • Wärmepumpen